额定容量 Rated Capacity(kVA) |
电压组合 Voltage combination |
联结组标号 |
空载损耗 |
不同的绝缘耐热等级下的负载损耗load Loss (W) |
空载电流 |
短路阻抗 |
||||
NO-load Current(%)) |
NO-load Short-circuit Impedance(%) |
|||||||||
高压(KV)HV |
高压分接范围Tapping Range of HV |
低压(KV)LV |
Connection symbol |
NO-load Loss (W) |
B(100℃) |
F(120℃) |
H(145℃) |
|||
800 |
35-38.5 |
±5 ±2x2.5 |
3.15 6 6.3 10 10.5 11 |
Dyn11 Yd11 YynO |
2500 |
9400 |
9900 |
10600 |
1.1 |
6.0 |
1000 |
2970 |
10800 |
11500 |
12300 |
1.1 |
|||||
1250 |
3480 |
12800 |
13600 |
14500 |
1.0 |
|||||
1600 |
4100 |
15400 |
16300 |
17400 |
1.0 |
|||||
2000 |
4700 |
18100 |
19200 |
20600 |
0.9 |
7.0 |
||||
2500 |
5400 |
21700 |
23000 |
24600 |
0.9 |
|||||
3150 |
6700 |
24300 |
25800 |
27500 |
0.8 |
8.0 |
||||
4000 |
7800 |
29400 |
31000 |
33000 |
0.8 |
|||||
5000 |
9300 |
34700 |
36800 |
39300 |
0.7 |
|||||
6300 |
11000 |
40500 |
43000 |
45900 |
0.7 |
|||||
8000 |
Dyn11 Yd11 Ynd11 |
12600 |
45700 |
48500 |
51900 |
0.6 |
9.0 |
|||
10000 |
14400 |
55500 |
58500 |
62600 |
0.6 |
|||||
12500 |
6 6.3 10 10.5 11 |
17500 |
64000 |
68000 |
72700 |
0.5 |
||||
16000 |
21500 |
75500 |
80000 |
84800 |
0.5 |
|||||
20000 |
25500 |
85000 |
90000 |
96300 |
0.4 |
10.0 |